How to Size a Home Backup Battery: Capacity, Inverter Output, Surge and Solar Recharge

Updated November 6, 2026 9 min read

Affiliate disclosure: some links on this page are affiliate links. If you buy through them, FoxyEco may earn a commission at no extra cost to you. It does not change what we recommend. How FoxyEco is funded.

Disclosure: this guide contains partner links to BLUETTI and Nature’s Generator, marked as sponsored. FoxyEco may earn a commission if you buy through them, at no extra cost to you.

Short answer: a home backup battery needs to pass four separate tests. It needs enough energy (kWh) for your essential loads over the outage you plan for, plus inverter losses and a reserve. It needs enough continuous output (W) for the loads that run at the same time, and enough surge to start the largest motor. It needs the right voltage (120 V, 230 V or 120/240 V split-phase). And it needs a recharge plan if the outage can outlast the battery. A capacity figure that passes the first test but fails any of the others is the wrong size.

Start with a measured load list. If you do not have one yet, follow How to measure your essential loads first. Once you have the numbers, you can check every step below in the FoxyEco solar generator runtime and array sizing calculator.

Who this is for

Households choosing between a portable power station, a power station with expansion batteries, or an installed home battery. The arithmetic is the same for all three; installed systems usually have higher inverter efficiency and are sized by an installer under local code, but your own numbers let you check the quote.

Step 1: Daily energy, split by AC and DC

Add the watt-hours per day of every green (must-run) load on your worksheet. Keep two subtotals: loads that need AC from the inverter, and loads that can run from DC outputs such as 12 V car sockets or USB-C. DC loads avoid most inverter losses. Routers, LED lighting and phone or laptop charging are often available as DC.

Step 2: Add conversion losses and inverter idle draw

An inverter turns stored DC into AC with losses. As a planning assumption, use 85 to 90 percent efficiency for a portable station’s AC output and about 95 percent for its DC outputs, unless the manual gives a figure. Inverters also draw power just by being switched on. Manufacturers rarely publish this “idle” or “no-load” draw; 10 to 30 W is a common planning range for 1 to 3 kWh portable units. Over 24 hours, 20 W of idle draw is 480 Wh, which can be larger than your router’s consumption. If a refrigerator is on the list, the inverter stays on around the clock, so the idle draw counts in full.

Step 3: Days of autonomy

Decide how long you want to cover without recharging. One evening (6 to 8 hours), one day, or a multi-day event such as a California Public Safety Power Shutoff, which PG&E schedules around forecast wind and can run one to several days (see the PSPS planning guide). Multiply the daily energy, after losses, by the number of days.

Step 4: Usable capacity and reserve

A power station’s rated capacity is its nominal battery energy. Not all of it reaches your loads, and running to 0 percent leaves nothing for surprises. Divide the requirement by a usable fraction. For planning, 0.80 to 0.85 is reasonable for portable units; installed home batteries often publish a usable kWh figure directly. Two further adjustments apply. Cold reduces available capacity, and LiFePO4 stations generally will not accept a charge below about 0 °C unless they have self-heating (see the winter LiFePO4 comparison). Capacity also fades with age; many LiFePO4 stations quote cycle life to 70 or 80 percent of original capacity, so a system sized exactly for today has less margin in year eight.

The formula, in one line:

Nominal capacity (Wh) = [(AC Wh ÷ AC efficiency) + (DC Wh ÷ DC efficiency) + (idle W × hours on)] × days ÷ usable fraction

Step 5: Continuous output and surge

Add the running watts of every load that can run at the same moment, then add about 25 percent headroom. That is the minimum continuous inverter rating. For surge, take the largest start-up demand and add the running watts of everything else that may already be on. Check the inverter’s surge rating and how long it can hold it; some manufacturers quote a surge that lasts only milliseconds. Motor loads such as well pumps and older compressors are where undersized inverters fail.

Step 6: Voltage

US homes use 120/240 V split-phase. Most portable stations output 120 V only, which cannot run a 240 V well pump, a 240 V furnace or a dryer circuit. Larger units and paired systems from several brands offer 120/240 V. UK and EU homes use single-phase 230 V, so this test is usually simpler there, although three-phase homes exist in parts of Europe. Supplying any fixed circuit requires a listed transfer switch, interlock or manufacturer home panel installed by a licensed electrician; never backfeed through a wall outlet.

Step 7: Solar or other recharge

Estimate daily solar harvest as panel watts × peak sun hours × a derate for heat, wiring, angle and controller losses. A derate of 0.70 to 0.80 is a common planning range. Use NREL’s PVWatts for your location and month rather than a national average: December in Seattle and June in Phoenix are very different. Then check that the panels fit the station’s solar input limits in volts, amps and watts, which is covered in Solar panels for a power station: check more than watts.

Three worked examples

All figures below are illustrative assumptions, stated so you can replace them. None is a measurement of a specific product.

A. Apartment essentials, one evening to one day

Loads: router on 12 V DC (432 Wh/day), LED lamps on DC or USB (180 Wh), phone and laptop on USB-C (180 Wh), plus 400 Wh of AC loads such as a small TV and a fan. Inverter on 12 hours only.

A 1 kWh class station covers an evening; a 2 kWh class station covers the full day. Continuous output is small, so a 1,000 to 1,800 W inverter is plenty. Running the router from AC instead of DC would keep the inverter on for the other 12 hours too, adding roughly 300 Wh of nominal capacity once the extra idle draw and conversion losses are counted.

B. Refrigerator, CPAP and communications, 48-hour shutoff

Loads: refrigerator 1,150 Wh/day (logged), CPAP without heated humidifier 40 W × 8 h = 320 Wh, router 432 Wh, lights 180 Wh, devices 180 Wh. Everything on AC for simplicity; inverter on 48 hours.

That is a 2 kWh class station plus one matching expansion battery, or a single 4 kWh class unit, with roughly 400 W of compatible panels. Continuous output: fridge 140 W + CPAP 40 W + small loads about 100 W, with a fridge start of roughly 600 W, so any 1,500 W or larger inverter passes. The battery size here is set by duration, not power. Medical device users should confirm power requirements with the device manufacturer and clinician.

C. Partial home through a transfer switch, three days, US 240 V well

Loads: 240 V well pump 1,000 W running for 2 hours a day (2,000 Wh), with a start-up surge assumed at 4,000 W; furnace blower 350 W × 8 h (2,800 Wh); refrigerator 1,150 Wh; lights and devices 800 Wh. Total 6,750 Wh/day. Assume an installed or large split-phase system at 0.92 efficiency, usable fraction 0.90, idle 40 W.

The inverter requirement is modest; the energy requirement is large. This household has three realistic options: a battery of roughly that size, a smaller battery plus a solar array large enough for winter, or a battery for short outages combined with a generator for long ones. The trade-offs are covered in home battery vs dual-fuel generator, and the long-run cost of each kWh in the home battery lifecycle cost worksheet.

Common sizing mistakes

Limits of this method

These steps give a planning estimate. Real runtime depends on temperature, battery age, actual inverter efficiency at your load level and how strictly the household sticks to the list. Installed systems connected to house wiring must be designed and permitted under the electrical code your jurisdiction has adopted, including NEC Article 702 for optional standby systems and Article 706 for energy storage in the US. Fire codes such as NFPA 855, and the residential provisions in the International Residential Code, limit how much stored energy can be placed in garages, utility rooms and other locations; your installer and building department apply the edition in force locally.

Next steps

Run your numbers through the runtime calculator, then compare equipment that fits in the best portable power stations for home backup. If you are weighing battery chemistry for a long-life system, read LiFePO4 vs NMC for home batteries.

To check current manufacturer specifications for the two main backup classes worked through above, compare BLUETTI's expandable 1–4 kWh LiFePO4 stations for apartment and refrigerator-tier backup, or Nature's Generator 120/240 V split-phase systems for partial-home and well-pump circuits.

Sources